Resolution: 1 °F with unit of measure in Fahrenheit, 1 ° C with unit of measure in
Celsius.
Display: one red LED 3-digit displays 13.2 mm (0.51 in) high, one red LED 2-digit
display 13.2 mm (0.51 in) high, two LED bars (10 red LED), output status indicators,
indicators of the unit of measure of the temperature showed by the instrument.
Outputs: 3 relays: one 8 A @ 250 Vac relay for top heating group control (NO),
one 8 A @ 250 Vac relay for floor heating group control (NO), one 8 A @ 250 Vac relay
for chamber light control (NO); the maximum current allowed on terminal 26 is 10 A.
10 WORKING SETPOINT AND CONFIGURATION PARAMETERS
10.1 Working setpoint
LABEL MIN. MAX. U.M. DEF. WORKING SETPOINT
rA1 rA2 °C/°F
(6)
0 working setpoint
10.2 First level parameters
LABEL MIN. MAX. U.M. DEF. PASSWORD
PA -90 100 --- 0 password
LABEL MIN. MAX. U.M. DEF. MEASURE INPUTS
/1 -10 10 °C/°F
(6)
0 chamber probe calibration
LABEL MIN. MAX. U.M. DEF. REGULATOR
rA0 -15 -1 °C/°F
(6)
-2 hysteresis (differential, it is relative to the working setpoint)
10.3 Second level parameters
LABEL MIN. MAX. U.M. DEF. MEASURE INPUTS
/0 10 11 --- 10 kind of probe (10 = “J” Tc, 11 = “K” Tc)
/1 -10 10 °C/°F
(6)
0 chamber probe calibration
/2 0 6 --- 3 probe reading speed (0 = fast, ... , 6 = slow)
/4 0 1 --- 0 display of non meaningful zeros (1 = YES)
/8 0 1 --- 1 unit of measure temperature (0 = Fahrenheit degree, 1 = Celsius degree)
LABEL MIN. MAX. U.M. DEF. REGULATOR
rA0 -15 -1 °C/°F
(6)
-2 hysteresis (differential, it is relative to the working setpoint)
rA1 0 rA2 °C/°F
(6)
0 minimum value you can assign to the working setpoint
rA2 rA1 999 °C/°F
(6)
300 maximum value you can assign to the working setpoint
LABEL MIN. MAX. U.M. DEF. FIRST ALARM
AA0 1 99 °C/°F
(6)
2 hysteresis (differential, it is relative to AA1, it is important if AA4 ≠ 1)
AA1 -99 999 °C/°F
(6)
0 first temperature alarm threshold (it is important if AA4 ≠ 1); look at AA4 as well
AA3 0 999 min 0 first temperature alarm exclusion time since you turn the instrument ON (it is important if
AA4 ≠ 1)
AA4 1 7 --- 1 kind of temperature alarm (1 = it will never be activated, 2 = absolute lower temperature
alarm, 3 = absolute upper temperature alarm, 4 = lower temperature alarm relative to the
working setpoint, 5 = upper temperature alarm relative to the working setpoint,
6 = lower temperature alarm relative to the working setpoint with automatic calculation and
enabling, 7 = upper temperature alarm relative to the working setpoint with automatic
calculation and enabling)