EVCO S.p.A. c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 73 of 116
Networks /
UART1 (1)
Stop - - - - - - - - - 1 BIT
Modbus communication stop bit number in a
RS-485 network wired on the first RS-485
port
1 BIT = 1 bit
2 BIT = 2 bit
Networks /
UART2 (2)
Address 1 247 - - - 1
local (or of the controller) Modbus node
address in a RS-485 network wired on the
second RS-485 port
Networks /
UART2 (2)
Baud Rate - - - - - - - - - 9600
Modbus communication baud rate in a
RS-485 network wired on the second
RS-485 port
1200 = 1,200 baud
2400 = 2,400 baud
4800 = 4,800 baud
9600 = 9,600 baud
19200 = 19,200 baud
28800 = 28,000 baud
38400 = 38,400 baud
57600 = 57,600 baud
Networks /
UART2 (2)
Parity - - - - - - - - - EVEN
Modbus communication parity in a RS-485
network wired on the second RS-485 port
NONE = no parity
ODD = odd
EVEN = even
Networks /
UART2 (2)
Stop - - - - - - - - - 1 BIT
Modbus communication stop bit number in a
RS-485 network wired on the second
RS-485 port
1 BIT = 1 bit
2 BIT = 2 bit
Networks /
UART2 (2)
Timeout 2 240 s 10
Modbus communication time-out in a
RS-485 network wired on the second
RS-485 port for the test of the remote values
of the I / O (after this time without Modbus
communication, the request is considered
not sent and the controller moves to the
following request) (3)
Password Level 1: -32768 32767 - - - 0
value of the password to gain access to
level 1